20 kVA Smart-UPS VT offers centralized 3 Phase UPS power protection with the reliability of the award winning Smart-UPS family. Ideal for small data centers, large retail stores, regional offices, and dense power requirements, the Smart-UPS VT includes dual-mains input, automatic and maintenance bypasses, and scalable runtime with hot-swappable batteries for increased availability. The rack mounted version maximizes valuable floor space by incorporating UPS, power distribution, and additional battery capacity in a single rack. Low cost of ownership is achieved through best-in-class efficiency and a reduction in rating of electrical infrastructure – wires, transformers, and generators due the Smart-UPS VT’s Soft Start feature.
Output
• Output power capacity- 16.0 KWatts / 20.0 kVA
• Max Configurable Power- (Watts) 16.0 KWatts / 20.0 kVA
• Nominal Output Voltage- 120V , 208V , 208V 3PH
• Output Voltage Note- Configurable for 200 : 208 or 220V 3 Phase nominal output voltage
• Efficiency at Full Load- 93.0 %
• Output Voltage Distortion- Less than 5% at full load
• Output Frequency- (sync to mains) 57 – 63 Hz for 60 Hz nominal
• Output Frequency- (not synced) 60Hz +/- 0.1% for 60Hz nominal
• Other Output Voltages- 220
• Load Crest Factor- Unlimited
• Topology- Double Conversion Online
• Waveform type- Sine wave
• Bypass- Built-in Maintenance Bypass, Built-in Static Bypass
Input
• Nominal Input Voltage- 208V 3PH
• Input frequency- 40 – 70 Hz
• Input Connections- Hard Wire 5-wire (3PH + N + G)
• Input voltage range for main operations- 177 – 239 (208V)V
• Efficiency at Full Load- 93.0 %
• Other Input Voltages- 220
• Input Power Factor at Full Load- 0.98
Batteries & Runtime
• Battery type- VRLA
• Included Battery Modules- 4
• Typical recharge time- 3hour(s)
• Replacement Battery- SYBT4
• Expected Battery Life (years)- 3 – 5
• RBC Quantity- 4
Communications & Management
• Interface Port(s)- SmartSlot
• Pre-Installed SmartSlot™ Cards- AP9617
• Control panel- Multi-function LCD status and control console
• Audible Alarm- Audible and visible alarms : configurable delays
• Emergency Power Off (EPO)- Optional
Physical
• Maximum Height- 78.54inches ( 1995mm , 199.5CM )
• Maximum Width- 23.62inches ( 600mm , 60.0CM )
• Maximum Depth- 42.32inches ( 1075mm , 107.5CM )
• Net Weight- 2090.0lbs. ( 950.0KG )
• Shipping weight- 2167.0lbs. ( 985.0KG )
• Shipping Height- 78.54inches ( 1995mm , 199.5CM )
• Shipping Width- 23.62inches ( 600mm , 60.0CM )
• Shipping Depth- 42.32inches ( 1075mm , 107.5CM )
Environmental
• Operating Temperature- 32 – 104 °F ( 0 – 40 °C )
• Operating Relative Humidity- 0 – 95 %
• Operating Elevation- 0-3333ft ( 0-999.9meters )
• Storage Temperature- -50 – 40 °C
• Storage Relative Humidity- 0 – 95 %
• Storage Elevation- 0-50000ft ( 0-15000meters )
• Audible noise at 1 meter from surface of unit- 58.0dBA
• Online thermal dissipation- 4238.0BTU/hr