Liebert has reinvented the double-conversion UPS. The Npower is the result of an international design collaboration and more than a decade of advanced research.
Every aspect of the Npower shows careful design and attention to detail. The rugged powertrain and advanced ActiveStarn.t controls were subjected to computer simulations and thermal analysis to ensure reliable performance in every environment.
Even the physical packaging is uniquely efficient, to make fully configured systems more compact than other products on the market.
Best of all, it’s a Liebert product designed to give the same million-hour critical bus lVITBF as its older brothers.
• Unmatched heritage of reliability and availability
• Smallest system footprint
• Excellent efficiency with nonlinear loads and partial loads
• Outstanding dynamic response
• All-digital ActiveStar controls and graphical user interface
Input
• Voltage- 208 or 480VAC, 60 Hz 3 Phase, 3-or 4-wire Plus ground
• Voltage Range- +10,-15% (no battery discharge at -20%)
• Frequency Range- 60Hz, +/-5
• Current Distortion- 10% maximum reflected THD at full load with optional input filter; 30% THD without filter
• Current Limit- 115% of full load input current
• Current Walk-in- 20 seconds full load
• Power factor- 0.80 lagging minimum at full load; up to 0.96 lagging at full load with optional input filter.
Environmental
• Operating Temperature- 32° to 104°F (0-40°C)
• Non-Operating Temperature- -4° to 158°F (-20° to 70°C)
• Relative Humidity 0-95% non-condensing
• Operating Altitude- Up to 6600 ft. (2000m) without derating
• Acoustical Noise- Less than 65dBA Typical, measured 3.3 (1m) ft from the unit
Output
• Voltage- 208 or 480VAC, 3-phase, 4-wire plus ground
• Voltage Adjustment Range- +/-5%
• Voltage Regulation- +/-0.5% for balance load, +/-1.0% for 100% unbalanced load
• Dynamic Regulation- +/-5% deviation for 100% load step, +/-1% for loss or return of AC input
• Transient Response Time- Recover to +/-1% of steady state within 1 cycle
• Voltage Distortion- For linear loads, 1% THD; less than 2.5% THD for 100% nonlinear loads w/o kVA/kW derating
• Phasing Balance- 120° +/-0.5° for balanced load. 120° +/-1° for 100% unbalanced load
• Frequency Regulation- +/-0.1%
• Load Power Factor Range- 1.0 to 0.7 lagging without derating
• Overload- 125% of full load for 10 minutes, 150% for 1 Minute w/ true sinusoidal waveform
Weights and Dimensions
• Width- 49.2 (in)
• Depth- 32.5 (in)
• Height- 71 (in)
• Weight- 2800 (LB)